The Environment Agency comment as follows on the proposal:- Any facilities
for the storage of oils, fuels or chemicals shall be sited on impervious
bases and surrounded by impervious bund walls. The volume of the bunded
compound should be at least equivalent to the capacity of the tank plus 10%
If there is multiple tankage, the compound should be at least equivalent to
the capacity of the largest tank, or the combined capacxity of inter-
connected tanks, plus 10%. All filling points, vents, gauges and sight
glasses must be located within the bund. The drainage system of the bund
shall be sealed with no discharge to any watercourse, land or underground
strata. Associated pipework should be located above ground and protected
from accidental damage. All filling points and tank overflow pipe outlets
should be detailed to discharge downwards into the bund. To prevent
pollution of the water environment. |