| No. | Condition Text |
|---|---|
| 1. | Condition 9 of pp. 06/23/0928/F requires details of any Air Source Heat Pumps (ASHP) on the building including their design, location and sound levels (to be expressed in dB). The following information was submitted: - Heating layout roof level main teaching block sheet 1 of 2. Dwg No. FE004-CAL-MB-RF-D-M-3410. Rev. P02. - Heating layout roof level main teaching block sheet 2 of 2. Dwg No. FE004-CAL-MB-RF-D-M-3411. Rev. P02. - Plantroom roof level main block. Dwg No. FE004-CAL-MB-RF-D-M-4302. Rev. P03. - Heating layout second floor sports block. Dwg No. FE004-CAL-SB-02-D-M-3407. Rev. P05. - Air Source Heat Pump Spec Sheet: PUZ-WZ85/100/120V/YAA . Ecodan R290. - Technical Note: Plant Noise Assessment. Doc No. FE004 - CDC - 00- ZZ - T- J - 3552. Rev. P01-S04 dated 19/05/2026. Upon full assessment of the submitted details, these are acceptable and are hereby approved. The ASHP shall be installed and operated only in accordance with the approved details prior to first occupation of any building they relate to, and shall be retained and operated as such thereafter. All ASHP shall be installed and maintained in accordance with manufacturers guidance with appropriate continued use of noise emission mitigations. |